Lenze TCF Series User Manual
Page 14

6 .1
INSTALLATION AFTER A LONG PERIOD OF STORAGE
STOP!
Severe	damage	to	the	drive	can	result	if	it	is	operated	after	a	long	period	of	
storage	or	inactivity	without	reforming	the	DC	bus	capacitors!
If	input	power	has	not	been	applied	to	the	drive	for	a	period	of	time	exceeding	three	years	
(due	to	storage,	etc),	the	electrolytic	DC	bus	capacitors	within	the	drive	can	change	internally,	
resulting	in	excessive	leakage	current .	This	can	result	in	premature	failure	of	the	capacitors	
if	the	drive	is	operated	after	such	a	long	period	of	inactivity	or	storage .
In	order	to	reform	the	capacitors	and	prepare	the	drive	for	operation	after	a	long	period	of	
inactivity, apply input power to the drive for 8 hours prior to actually operating the motor .
6 .2
EXPLOSION PROOF APPLICATIONS
Explosion	proof	motors	that	are	not	rated	for	inverter	use	lose	their	certification	when	used	
for	variable	speed .	Due	to	the	many	areas	of	liability	that	may	be	encountered	when	dealing	
with	these	applications,	the	following	statement	of	policy	applies:
“Lenze AC Tech inverter products are sold with no warranty of fitness for a particular 
purpose or warranty of suitability for use with explosion proof motors. Lenze AC 
Tech accepts no responsibility for any direct, incidental or consequential loss, 
cost, or damage that may arise through the use of its AC inverter products in these 
applications. The purchaser expressly agrees to assume all risk of any loss, cost, or 
damage that may arise from such application."
10