NO. PARAMETER NAME
RANGE OF ADJUSTMENT
FACTORY
DEFAULT
(NOTE 1)
57
TB STRIP STATUS
(VIEW-ONLY)
(N/A)
58
KEYPAD STATUS
(VIEW-ONLY)
(N/A)
59
TB-30 OUTPUT
(VIEW-ONLY)
(N/A)
73
HEATSINK TEMP
(VIEW-ONLY)
(N/A)
79
INPUT ASSERTION
LEVEL
HIGH (01), LOW (02)
HIGH (01)
80
DRIVE MODE
CONSTANT V/Hz (01), VARIABLE V/Hz (02),
CONSTANT V/Hz
(01)
ENHANCED CONSTANT V/Hz (03),
ENHANCED VARIABLE V/Hz (04),
VECTOR SPEED (05), VECTOR TORQUE (06)
81
AUTO CALIBRATION
CALIBRATION NOT DONE (00),
CALIBRATION
NOT DONE (00)
CALIBRATION CYCLE ENABLED (01),
CALIBRATION COMPLETE (02)
82
CURRENT LOOP P GAIN
0 .00 - 16 .0
0 .25
83
CURRENT LOOP I GAIN
12 - 9990 mSEC
65 mSEC
84
STATOR RESISTANCE
0 .00 - 64 .0 OHMS (NOTE 3)
0 .00 OHMS
85
MOTOR RATED SPEED
300 - 65000 RPM
1750 RPM
86
MOTOR RATED AMPS
0 .0 - 480 AMPS
0 .0 AMPS
87
MOTOR RATED VOLTS
0 - 600 Vac
0 Vac
88
MOTOR BASE FREQ
25 - 500 Hz
60 Hz
91
MOTOR COSINE PHI
0 .40 - 0 .99
0 .80
92
MOTOR INDUCTANCE
0 .0 - 2000 mH (NOTE 3)
0 .0 mH
93
TORQUE LIMIT
0 - 400 %
100%
94
DRIVE PERSONALITY
(NOTE 4)
(NOTE 4)
95
MOTOR CURRENT
(VIEW-ONLY)
(N/A)
96
TORQUE PERCENT
(VIEW-ONLY)
(N/A)
NOTE 1: Factory defaults are shown for a 60 Hz base frequency . Refer to Parameter 48 for 50 Hz base frequency .
NOTE 3: This parameter is automatically set during the AUTO CALIBRATION function .
NOTE 4: Refer to Section 15 - DESCRIPTION OF PARAMETERS .
35