Lenze TCF Series User Manual
Page 45
![background image](/manuals/566128/45/background.png)
11 AUXILIARY STOP: When TB-13A is opened with respect to TB-4, the drive
will decelerate to a STOP (even if STOP METHOD is set to COAST) at the
rate programmed into Parameter 42 - ACCEL/DECEL #2 .
12 ACCEL/DECEL #2: Selects the acceleration and deceleration time
programmed into Parameter 42 - ACCEL/DECEL #2 .
NOTE
• In order for the RUN REVERSE and START REVERSE functions to operate,
Parameter 17 - ROTATION DIRECTION must be set to FORWARD AND
REVERSE (02) .
• If a -10 to +10 VDC bipolar speed reference is being used (Parameter 07
- BIPOLAR REFERENCE SELECTION is ENABLED), the RUN and START
functions on TB-13A will only start the drive, they will not select direction .
Direction is determined by the polarity of the -10 to +10 VDC signal .
P11
TB-13B FUNCTION SELECT
This selects the function of terminal TB-13B . Closing TB-13B to TB-4 (or opening in the case
of setting 07) activates the selected function . The following functions can be selected:
01 NONE: Disables the TB-13B function .
02 0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference
input .
03 4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference
input .
04 PRESET SPEED #2: Selects PRESET SPEED #2 as the AUTO speed
reference . The drive will operate at the frequency programmed in Parameter 32 .
05 DECREASE FREQUENCY: Decreases the speed setpoint when using the MOP
function . Refer to Section 10 .6 .
06 JOG FORWARD: Jog in the forward direction . In this mode, the drive will JOG
at the speed programmed into Parameter 32 - PRESET SPEED #2 . JOG is not
available in Vector Torque mode .
WARNING!
When operating in JOG mode, the STOP terminal (TB-1), the AUXILIARY
STOP function (setting 07), and the STOP key on the optional remote keypad
WILL NOT stop the drive . To stop the drive, remove the JOG command
NOTE
If the drive is commanded to JOG FORWARD while running, the drive will
enter JOG mode and run at PRESET SPEED #2 . When the JOG command
is removed, the drive will STOP .
07 AUXILIARY STOP: When TB-13B is opened with respect to TB-4, the drive
will decelerate to a STOP (even if STOP METHOD is set to COAST) at the
rate programmed into Parameter 42 - ACCEL/DECEL #2 .
41