NO. PARAMETER NAME
RANGE OF ADUSTMENT
FACTORY
DEFAULT
(NOTE 1)
11
TB-13B FUNCTION
SELECT
NONE (01), 0-10 VDC (02), 4-20 mA (03),
NONE (01)
PRESET SPEED #2 (04), DECREASE FREQ (05),
JOG FORWARD (06), AUXILIARY STOP (07)
12
TB-13C FUNCTION
SELECT
NONE (01), 0-10 VDC (02), 4-20 mA (03),
NONE (01)
PRESET SPEED #3 (04), INCREASE FREQ (05),
EXTERNAL FAULT (06), REMOTE KEYPAD (07),
DB FAULT (08), JOG REVERSE (09),
ACCEL/DECEL #2 (10)
13
TB-15 OUTPUT
(SEE PARAMETER 6 - TB-14 OUTPUT)
NONE (01)
14
CONTROL
TERMINAL STRIP ONLY (01),
TERMINAL STRIP
ONLY (01)
REMOTE KEYPAD ONLY (02),
TERMINAL STRIP OR REMOTE KEYPAD (03)
15
SERIAL LINK
DISABLE (01), 9600, 8, N, 2 WITH TIMER (02),
9600, 8, N, 2 WITHOUT TIMER (03),
9600, 8, E, 1 WITH TIMER (04),
9600, 8, N, 2
9600, 8, E, 1 WITHOUT TIMER (05),
WITH TIMER (02)
9600, 8, O, 1 WITH TIMER (06),
9600, 8, O, 1 WITHOUT TIMER (07)
17
ROTATION
FORWARD ONLY (01),
FORWARD
FORWARD AND REVERSE (02)
ONLY (01)
18 MTR OVERLOAD TYPE
SPEED COMP (01), NO COMP (02)
SPEED COMP (01)
19
ACCELERATION TIME
0 .1 - 1300 .0 SEC
20 .0 SEC
20
DECELERATION TIME
0 .1 - 1300 .0 SEC
20 .0 SEC
21
DC BRAKE TIME
0 .0 - 999 .0 SEC
0 .0 SEC
22
DC BRAKE VOLTAGE
0 .0 - 30 .0 %
0 .00%
23 MINIMUM FREQUENCY
0 .0 - MAXIMUM FREQUENCY
0 .0 Hz
24 MAXIMUM FREQUENCY
MINIMUM FREQ - 240 .0 Hz
60 .0 Hz
25
CURRENT LIMIT
50 - 200 % (NOTE 2)
200%
26
MOTOR OVERLOAD
30 - 100 %
100%
27
BASE FREQUENCY
25 .0 - 500 .0 Hz
60 .0 Hz
NOTE 1: Factory defaults are shown for a 60 Hz base frequency . Refer to Parameter 48 for 50 Hz base frequency .
NOTE 2: If LINE VOLTAGE is set to LOW, maximum setting is 167% .