Lenze TCF Series User Manual
Page 38
![background image](/manuals/566128/38/background.png)
NO. PARAMETER NAME
RANGE OF ADJUSTMENT
FACTORY
DEFAULT
(NOTE 1)
28
FIXED BOOST
0 .0 - 30 .0 %
1 .0 %
29
ACCEL BOOST
0 .0 - 20 .0 %
0 .0 %
30
SLIP COMPENSATION
0 .0 - 5 .0 %
0 .0 %
31-37
PRESET SPEEDS
0 .0 - MAXIMUM FREQUENCY
0 .0 Hz
38
SKIP BANDWIDTH
0 .0 - 10 .0 Hz
0 .0 Hz
39
SPEED SCALING
0 .0 - 6500 .0
0 .0
40
FREQUENCY SCALING
3 .0 - 1200 .0 Hz
60 .0 Hz
41
LOAD SCALING
10 - 200 %
200 %
42
ACCEL/DECEL #2
0 .1 - 1300 .0 SEC
20 .0 SEC
43
SERIAL ADDRESS
1 - 247
1
44
PASSWORD
000 - 999
225
45
SPEED AT MIN SIGNAL
0 .0 - 999 Hz
0 .0 Hz
46
SPEED AT MAX SIGNAL
0 .0 - 999 Hz
60 .0 Hz
47
CLEAR HISTORY
MAINTAIN (01), CLEAR (02)
MAINTAIN (01)
48
PROGRAM SELECTION
USER SETTINGS (01), OEM SETTINGS (02),
USER SETTINGS
(01)
RESET OEM (03), RESET 60 (04),
RESET 50 (05), TRANSLATE (06)
49
TB-13D
FUNCTION SELECT
NONE (01), 0-10 VDC (02), 4-20 mA (03),
NONE (01)
PRESET SPEED #1 (04),
START FORWARD (05),
EXTERNAL FAULT (06),
REMOTE KEYPAD (07), DB FAULT (08),
AUXILIARY STOP (09), ACCEL/DECEL #2 (10)
50
SOFTWARE CODE
(VIEW-ONLY)
(N/A)
51
SOFTWARE CODE
(VIEW-ONLY)
(N/A)
52
DC BUS VOLTAGE
(VIEW-ONLY)
(N/A)
53
MOTOR VOLTAGE
(VIEW-ONLY)
(N/A)
54
LOAD
(VIEW-ONLY)
(N/A)
55
0-10 VDC INPUT
(VIEW-ONLY)
(N/A)
56
4-20 mA INPUT
(VIEW-ONLY)
(N/A)
NOTE 1: Factory defaults are shown for a 60 Hz base frequency . Refer to Parameter 48 for 50 Hz base frequency .
34