Lenze TCF Series User Manual
Page 44
![background image](/manuals/566128/44/background.png)
P08
TB-30 ANALOG OUTPUT
Terminal TB-30 can be used as an analog output proportional to output frequency, load or
motor torque .
01
NONE
Disables TB-30 Output
02
0-10 VDC FREQUENCY
10 VDC = Setting of P40 - Frequency Scaling
03
2-10 VDC FREQUENCY
04
0-10 VDC LOAD
10 VDC = Setting of P41 - Load Scaling
05
2-10 VDC LOAD
06
0-10 VDC TORQUE
10 VDC = Setting of P93 - Torque Limit
07
2-10 VDC TORQUE
NOTE
The 2-10 VDC signal can be converted to a 4-20 mA signal by connecting a resistor
in series with the signal such that the total load resistance is 500 Ohms . However, this
output cannot be used with devices that derive power from a 4-20 mA signal .
P10
TB-13A FUNCTION SELECT
This selects the function of terminal TB-13A . Closing TB-13A to TB-4 (or opening in the
case of settings 08 and 11) activates the selected function . The following functions can be
selected:
01 NONE: Disables the TB-13A function .
02 0-10 VDC: Sets a 0-10V DC signal (at TB-5) as the AUTO speed reference input .
03 4-20 mA: Sets a 4-20 mA signal (at TB-25) as the AUTO speed reference input .
04 PRESET SPEED #1: Selects PRESET SPEED #1 as the AUTO speed
reference . The drive will operate at frequency programmed in Parameter 31 .
05 START FORWARD: Momentarily close TB-13A to TB-4 to START the drive in
the forward direction . Momentarily open TB-1 to TB-4 to STOP .
06 RUN REVERSE: Close TB-13A to TB-4 to RUN in the reverse direction, and
open to STOP . Close TB-1 to TB-4 to RUN in the forward direction, and open to
STOP .
07 START REVERSE: Momentarily close TB-13A to TB-4 to START the drive
in the reverse direction . Momentarily open TB-1 to TB-4 to STOP . For
forward operation, program TB-13D (Parameter 49) to START FORWARD .
Momentarily close TB-13D to TB-4 to START in the forward direction, and
momentarily open TB-1 to TB-4 to STOP .
08 EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input . If
TB-13A is open with respect to TB-4, the drive will fault .
09 REMOTE KEYPAD: Selects the optional remote keypad as the control source .
Refer to Parameter 14 - CONTROL .
10 DB FAULT: Sets TB-13A as a dynamic braking fault input when using the
optional dynamic braking module . When this input is activated by the dynamic
braking module, the drive will trip into a "dF" fault and the motor will coast to a
stop . Refer to the manual included with the Dynamic Braking option .
40