P13
TB-15 OPEN COLLECTOR OUTPUT
This selects the status indication for the open-collector output at TB-15, and has the same
selections as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT .
P14
CONTROL
This selects the source of START/STOP and direction commands .
01 TERMINAL STRIP ONLY: The drive will only respond to START/STOP and
direction commands from the terminal strip .
02 REMOTE KEYPAD ONLY: The drive will only respond to START/STOP and
direction commands from the optional remote keypad .
03 TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A, TB-13C, or
TB-13D can be used to select terminal strip control or remote keypad control .
Refer to Parameters 10, 12, and 49 .
NOTE
The STOP button on the optional remote keypad is always active as long as
the serial link remains intact .
P15
SERIAL LINK
This parameter configures the drive for Modbus RTU serial communications . The options are
listed by baud rate, number of data bits, parity, number of stop bits and whether the watchdog
timer is enabled or disabled .
WARNING!
Controlling the drive from the serial link without the watchdog timer could
cause damage to equipment and/or injury to personnel!
The watchdog timer will stop the drive after 10 seconds of no serial activity to safeguard
against a failed serial link . During set-up or troubleshooting it may be useful to disable the
watchdog timer but is it not recommended to run normally without the watchdog timer .
01 DISABLED: Disables the serial link
02 9600, 8, N, 2 - ENABLED WITH TIMER
03 9600, 8, N, 2 - ENABLED WITHOUT TIMER
04 9600, 8, E, 1 - ENABLED WITH TIMER
05 9600, 8, E, 1 - ENABLED WITHOUT TIMER
06 9600, 8, O, 1 - ENABLED WITH TIMER
07 9600, 8, O, 1 - ENABLED WITHOUT TIMER