14 parameter menu – Lenze TCF Series User Manual
Page 36
14
PARAMETER MENU
NO. PARAMETER NAME
RANGE OF ADJUSTMENT
FACTORY
DEFAULT
(NOTE 1)
01
LINE VOLTAGE
HIGH (01), LOW (02)
HIGH (01)
02
CARRIER FREQUENCY
2kHz (01), 4 kHz (02), 8 kHz (03)
4 kHz (02)
03
START METHOD
NORMAL (01), START ON POWER UP (02),
NORMAL (01)
START WITH DC BRAKE (03),
AUTO RESTART WITH DC BRAKE (04),
FLYING RESTART 1 (05),
FLYING RESTART 2 (06)
04
STOP METHOD
COAST (01), COAST WITH DC BRAKE (02),
COAST (01)
RAMP (03), RAMP WITH DC BRAKE (04)
05
STANDARD
REFERENCE SOURCE
speed mode: KEYPAD (01), PRESET #1 (02),
KEYPAD (01)
0-10 VDC (03), 4-20 mA (04)
torque mode: KEYPAD (01), KEYPAD (02),
0-10 VDC (03), 4-20 mA (04)
06
13
TB-14 OUTPUT
TB-15 OUTPUT
NONE (01), RUN (02), FAULT (03),
NONE (01)
NONE (01)
INVERSE FAULT (04), FAULT LOCKOUT (05),
AT SET SPEED (06), ABOVE PRESET #3 (07),
CURRENT LIMIT (08), AUTO SPEED (09),
REVERSE (10), DYNAMIC BRAKING (11)
07
BIPOLAR REFERENCE
SELECTION
DISABLE (01), ENABLE (02)
DISABLE (01)
08
TB-30 OUTPUT
NONE (01), 0-10 VDC FREQ (02),
NONE (01)
2-10 VDC FREQ (03), 0-10 VDC LOAD (04),
2-10 VDC LOAD (05), 0-10 VDC TORQUE (06),
2-10 VDC TORQUE (07)
10
TB-13A
FUNCTION SELECT
NONE (01), 0-10 VDC (02), 4-20 mA (03),
NONE (01)
PRESET SPEED #1 (04),
START FORWARD (05), RUN REVERSE (06),
START REVERSE (07), EXTERNAL FAULT (08),
REMOTE KEYPAD (09), DB FAULT (10),
AUXILIARY STOP (11), ACCEL/DECEL #2 (12)
NOTE 1: Factory defaults are shown for a 60 Hz base frequency . Refer to Parameter 48 for 50 Hz base frequency .