7 .2
INPUT FUSING & DISCONNECT REQUIREMENTS
A circuit breaker or a disconnect switch with fuses must be provided in accordance with the
National Electric Code (NEC) and all local codes . Refer to the following tables for proper
fuse/circuit breaker ratings and wire sizes .
INPUT FUSE & CIRCUIT BREAKER RATINGS
208/240 Vac, 1 phase 208/240 Vac, 3 phase 400/480 Vac, 3 phase
480/590 Vac, 3 phase
MODEL
RATING
MODEL
RATING
MODEL
RATING
MODEL
RATING
TF205Y
10 A
TF205Y
10 A
TF405
10 A
TF210Y
15 A
TF210(Y)
10 A
TF410
10 A
TF510
10 A
TF215Y
20 A
TF215(Y)
12 / 10 A
TF415
10 A
TF220Y
25 / 20 A
TF220(Y)
15 / 12 A
TF420
10 A
TF520
10 A
TF230Y
30 / 25 A
TF230(Y)
20 / 15 A
TF430
10 A
TF530
10 A
TF250
30 / 25 A
TF450
15 A
TF550
12 A
TF275
45 / 40 A
TF475
20 A
TF575
20 A
TF2100
50 / 50 A
TF4100
30 / 25 A
TF5100
20 A
NOTE
• Applicable national and local electrical codes take precedence over
recommendations in these tables .
• Use UL Class CC fast-acting, current limiting type fuses . Select fuses
with low I2T values, rated at 200,000 AIC . Recommended fuses are
Bussman KTK-R, JJN, and JJS . Similar fuses with equivalent ratings by
other manufacturers may also be acceptable .
WARNING!
This product can cause a DC current in the protective conductor . Where
a residual current device (RCD) is used for protection in case of direct or
indirect contact, only an RCD of Type B is allowed on the supply side of
this product . Otherwise, another protective measure shall be applied, such
as separation from the environment by double or reinforced insulation, or
isolation from the supply system by a transformer .
Observe the following when using RCDs:
1 . Only install the RCD between the supply mains and drive controller .
2 . The RCD can be activated by:
•
capacitive leakage currents between the cable screens during
operation (especially with long, screened motor cables)
•
connecting several drives to the mains at the same time
•
additional RFI filters
12