Commissioning – Lenze E82EV 8200 User Manual
Page 151

Commissioning
Important codes for quick commissioning
l
151
EDK82EV113 DE/EN/FR 11.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0007
v
uSEr
(Cont.)
E4
E3
E2
E1
41
JOG1/3
DCB
TRIP−Set
DFIN1−ON
42
QSP
DCB
TRIP−Set
DFIN1−ON
43
CW/CCW
QSP
TRIP−Set
DFIN1−ON
44
UP
DOWN
PAR
DFIN1−ON
45
CW/CCW
QSP
PAR
DFIN1−ON
46
H/Re
PAR
QSP
JOG1/3
47
CW/QSP
CCW/QSP
H/Re
JOG1/3
48
PCTRL1−
OFF
DCB
PCTRL1−I−
OFF
DFIN1−ON
49
PCTRL1−
OFF
JOG1/3
QSP
DFIN1−ON
50
PCTRL1−
OFF
JOG1/3
PCTRL1−I−
OFF
DFIN1−ON
51
DCB
PAR
PCTRL1−I−
OFF
DFIN1−ON
255
Free configuration in C0410
Read only
Do not change C0007 since settings
in C0410 may get lost
C0010
uSEr
Minimum
output
frequency
0.00
0.00
à 14.5 Hz
{0.02 Hz}
650.00
l
C0010 not effective in the case of
bipolar setpoint selection (−10 V ...
+ 10 V)
l
C0010 only limits the analog
input 1
l
In the case of a max. output
frequency > 50 Hz the switching
threshold of the auto DCB in
C0019 has to be increased.
l
From software 3.5: If
C0010 > C0011, the drive does
not start when controller enable
is set.
à Speed setting range 1 : 6 for Lenze
geared motors: For operation
with Lenze geared motors has to
be set necessarily.
C0011
uSEr
Maximum
output
frequency
50.00
7.50
à 87 Hz
{0.02 Hz}
650.00
C0012
uSEr
Acceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00
Reference: frequency change 0 Hz ...
C0011
l
Additional setpoint
ðC0220
l
Acceleration times that can be
activated via digital signals
ð
C0101
C0013
uSEr
Deceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00
Reference: frequency change C0011...
0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times that can be
activated via digital signals
ð
C0103