Commissioning – Lenze E82EV 8200 User Manual
Page 144

Commissioning
Parameter setting with the XT EMZ9371BC keypad
Vector control
l
144
EDK82EV113 DE/EN/FR 11.0
Comment
Switch−on sequence
12.
Activate the operating mode "vector control" (C0014 = 4)
Lenze setting: Linear V/f characteristic control (C0014 = 2)
13.
Enter the motor data
See motor nameplate
A
Rated motor speed (C0087)
Lenze setting: 1390 rpm
B
Rated motor current (C0088)
Lenze setting: depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
C
Rated motor frequency (C0089)
Lenze setting: 50 Hz
D
Rated motor voltage (C0090)
Lenze setting: depending on the controller
Enter the value for the motor circuit
configuration (star/delta) selected!
E
Motor cos
j (C0091)
Lenze setting: depending on the controller
14.
Start the motor parameter identification (C0148)
Only when the motor is cold!
A
Ensure that the controller is inhibited
Terminal X3/28 = LOW
B
Set C0148 = 1
Press
TV
C
Enable the controller
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment
c is off
– The motor consumes current and makes a
high−pitched" tone.
– The motor does not rotate!
D
If segment
c becomes active again after approx. 30 s,
inhibit controller again.
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) = Total
resistance of motor cable and motor
15.
Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off
Possible settings
(
¶ 153)
When all settings are complete:
16.
Select setpoint
E.g. via potentiometer at terminals 7, 8, 9
17.
Enable the controller
Terminal X3/28 = HIGH
18.
The drive is now running.
If the drive does not start, additionally press
u