Vector control, Commissioning – Lenze E82EV 8200 User Manual
Page 143

Commissioning
Parameter setting with the XT EMZ9371BC keypad
Vector control
l
143
EDK82EV113 DE/EN/FR 11.0
Vector control
The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.
Switch−on sequence
Comment
1.
Plug in the keypad
2.
Ensure that controller inhibit is active after mains
connection
Terminal X3/28 = LOW
3.
Switch on the mains
4.
After approx. 3 s the keypad is in the operating level and
displays the output frequency (C0050) and the device
utilisation (C0056)
5.
For quick commissioning you select the "Quick start"
menu
The submenu "VectorCtrl qu" contains the codes
which you require for commissioning a standard
application. The digital inputs are configured in
Lenze setting:
X3/E1, X3/E2: activation of fixed setpoints (JOG)
X3/E3: activation of DC injection brake (DCB)
X3/E4: CW rotation/CCW rotation
A
Change the menu level with
V
B
Change to the "Quick start" menu and there to the
"VectorCtrl qu" submenu with
z z Z z
C
Change to the code level with
Z to parameterise your
drive
6.
Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)
7.
If required, adapt the fixed setpoints JOG.
A
JOG 1 (C0037)
Lenze setting: 20 Hz
Activation:
X3/E1 = HIGH, X3/E2 = LOW
B
JOG 2 (C0038)
Lenze setting: 30 Hz
Activation:
X3/E1 = LOW, X3/E2 = HIGH
C
JOG 3 (C0039)
Lenze setting: 40 Hz
Activation:
X3/E1 = HIGH, X3/E2 = HIGH
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
11.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s