C13858 | ethernet port statistics, C13861 | cip module status, C13862 | cip network status – Lenze E84Dxxxx User Manual
Page 98: C13861, C13862, 13 parameter reference

13
Parameter reference
13.1
Parameters relevant for communication
98
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13858
C13861
C13862
Parameter | Name:
C13858 | Ethernet Port Statistics
Data type: UNSIGNED_32
Index: 10717
d
= 29DD
h
Display of statistical values for the data transfer via the Ethernet connections
Subcodes
Info
C13858/1
Ethernet port X31: RX
C13858/2
Ethernet port X31: RX CRC error
C13858/3
Ethernet port X31: RX discarded
C13858/4
Ethernet port X31: TX
C13858/5
Ethernet port X31: TX discarded
C13858/6
Ethernet port X32: RX
C13858/7
Ethernet port X32: RX CRC error
C13858/8
Ethernet port X32: RX discarded
C13858/9
Ethernet port X32: TX
C13858/10
Ethernet port X32: TX discarded
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13861 | CIP Module Status
Data type: UNSIGNED_16
Index: 10714
d
= 29DA
h
Display of the current CIP module status
(Instance attribute 8 (State) in the
Identity Object (1 / 0x01) ( 108)
• The status is also signalled by means of the NS LED.
Selection list
(read only)
0 Nonexistent
1 Device Self Testing
2 Standby
3 Operational
4 Major Recoverable Fault
5 Major Unrecoverable Fault
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13862 | CIP Network Status
Data type: UNSIGNED_16
Index: 10713
d
= 29D9
h
Display of the current CIP network status
• The status is also signalled by means of the NS LED.
Selection list
(read only)
0 No IP Address
1 Nonexistent
2 Established
3 Timed Out
4 Duplicate IP
5 Self-Test
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT