2 "ac drive profile" application, Ac drive profile" application, 8i/o data transfer (implicit messages) – Lenze E84Dxxxx User Manual
Page 45
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
45
8
I/O data transfer (implicit messages)
8.2
Technology applications (TA) / drive profiles
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.2.2
"AC Drive Profile" application
The "AC Drive Profile" contains ...
• the data basis for motor parameters,
• management functions of the motor control devices,
• Device-specific functions of the inverter, e.g. speed ramps, torque control etc.
For using the "AC Drive Profile", the following assembly object instances in the host (scanner) have
to be used:
See also:
•
•
Tip!
Here you will find information on configuring with the »RSLogix 5000« programming
software from Rockwell:
I/O configuration with »RSLogix 5000« version 19 or lower
I/O configuration with »RSLogix 5000« version 20 or higher
Instance ID
Assembly object instance
[dec]
[hex]
20
0x14
Basic Speed Control Output
Outputs: From the scanner to
the adapter
21
0x15
Extended Speed Control Output
22
0x16
Speed and Torque Control Output
23
0x17
Extended Speed and Torque Control Output
70
0x46
Basic Speed Control Input
Inputs: From the adapter to
the scanner
71
0x47
Extended Speed Control Input
72
0x48
Speed and Torque Control Input
73
0x49
Extended Speed and Torque Control Input
Reference manual / »Engineer« online help for Inverter Drives 8400 protec
Here you can find detailed information on how to use the "AC Drive Profile".