Parameter data transfer (explicit messages)
9.1
Write parameters
70
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.1
Write parameters
In order to write data into code C00011 of the Inverter Drive 8400 protec by means of explicit
message transfer, for example, the following settings are necessary:
Settings
Value / description
Message Type
"CIP Generic"
Service Type
"Set Attribute Single" (service code "0x10")
Class
"0x6E" (access to Lenze code)
Instance
"11" = Lenze code C00011 of Inverter Drive 8400 protec
Attribute
"1" = Subcode of the Lenze code
• If the corresponding Lenze code does not have a subcode, the value ’1’
must be entered here.
• A display code cannot be configured by the "SET" service.
Source Element
Variable in the PLC program used as data source for writing.
Source Length
For writing to code C00011, set the source length to "2 bytes".