3 lenze class (104 / 0x68), Lenze class (104 / 0x68) ( 141), Lenze class (104 / 0x68) – Lenze E84Dxxxx User Manual
Page 141: 14 implemented cip™ objects
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
141
14
Implemented CIP™ objects
14.4
Lenze objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.4.3
Lenze Class (104 / 0x68)
The "Lenze Class (104 / 0x68)" provides the image of the scanner output data.
The output data of the scanner are sent by means of the assembly object instance 110 (0xE5,
Custom Output) and are provided at the MCI_IN interface of the communication module.
Class attributes
Instance attributes
Supported service codes
Attribute
ID
Service
Name
Data type
Value
1
Get
Revision
UINT
2 (0x0002)
2
Get
Max. Instance
UINT
1 (0x0001)
Attribute
ID
Service
Name
Data type
Value
1
Get
No. of supported Attributes
USINT
3 (0x0003)
2
Get
Attribute List
USINT
1 (0x0001) ... 3 (0x0003)
3
Get
I/O image of consumed data USINT
Image of the scanner output data
Service code
[hex]
Name
Description
0x01
Get_Attributes_All
Outputs a list of the attributes and the attribute's values for
a certain object.
0x0E
Get_Attribute_Single
Outputs the value of a certain attribute.