4 technical data, Technical data, 4technical data – Lenze E84Dxxxx User Manual
Page 13
![background image](/manuals/565921/13/background.png)
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
13
4
Technical data
4.1
General data and operating conditions of the EtherNet/IP
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4
Technical data
4.1
General data and operating conditions of the EtherNet/IP
Mounting instructions/hardware manual for Inverter Drives 8400 protec
Here you can find information on general technical data, operating conditions, and rated
data of the device.
Range
Values
Communication profile
EtherNet/IP
Communication medium
S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT 5e
Interface for communication
RJ45 Standard Ethernet (in accordance with IEEE 802.3), 100Base-TX (Fast
Ethernet) or M124-socket (4-pole, D-coded)
Network topology
Tree, star, and line
Type of node
Adapter (slave)
Number of nodes
Max. 254 in the subnetwork
Max. cable length
100 m
Vendor ID
587 (0x24B), Lenze (’Lenze AC Tech’ in older Rockwell data)
Device type
2 (0x02), AC Drive
Product code
8410 (0x20DA)
Baud rate
• 10 Mbps
• 100 Mbps
Transmission mode
Half duplex / full duplex
Switching method
Store-and-forward / cut-through
Switch latency
Approx. 125 μs at max. telegram length