8.2
Technology applications (TA) / drive profiles
The Inverter Drives 8400 protec is provided with various drive profiles. They define a standardised
or individual control and status word assignment and the standardisation of setpoints and actual
value scalings.
The following drive profiles are supported by the inverter:
• Lenze technology applications / user-definable parameter sets
• "AC Drive Profile" application
8.2.1
Lenze technology applications / user-definable parameter sets
The technology applications integrated in the inverter provide the main signal flow for realising a
general or specific drive solution.
For using the Lenze technology application selection in the »Engineer« via standard device code
C00005, the following assembly object instances have to be used in the host (scanner):
The custom assemblies also allow for a user-definable parameter setting, depending on the
application. Hence, 16 data words (32 bytes) can be freely assigned with variables of the MCI port
blocks in the »Engineer«.
The user-definable parameter setting can be used in addition to the previously set technology
application.
Lenze technology application / configuring user-definable parameter sets
Tip!
Here you will find information on configuring with the »RSLogix 5000« programming
software from Rockwell:
I/O configuration with »RSLogix 5000« version 19 or lower
I/O configuration with »RSLogix 5000« version 20 or higher
Instance ID
Assembly object instance
[dec]
[hex]
110
0x6E
Custom Output
(from the adapter to the scanner)
111
0x6F
Custom Input
(from the adapter to the scanner)