11 diagnostics – Lenze E84Dxxxx User Manual
Page 76
![background image](/manuals/565921/76/background.png)
11
Diagnostics
11.1
LED status displays
76
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
NS
Green
Red
Off
Off
CIP network status: "No IP Address"
The device is not supplied with voltage or does not yet have an IP
address.
Off
On
CIP network status: "Duplicate IP"
The device has no access to the fieldbus (IP address conflict).
Off
Blinking
CIP network status: "Connection Timeout"
A time-out is executed.
On
Off
CIP network status: "Connected"
The device is working correctly and has established a connection to the
scanner.
Blinking
Off
CIP network status: "No Connections"
The device ...
• is working correctly;
• has been assigned an IP address;
• has not been integrated into the network by the scanner yet.
Blinking
Blinking
CIP network status: "Self-Test"
The device is in the state of self testing.
Err
Red
On
A communication error has occurred.
Lnk/Act1
Lnk/Act2
Yellow
On or
flickers
Data are exchanged via Ethernet.
LED
Colour / Status
Description
250 ms
250 ms
250 ms
250 ms
250 ms
250 ms
50 ms