C13881 | overall ethernet timeout time, C13885 | clear i/o data, C13899 | hostname – Lenze E84Dxxxx User Manual
Page 102: C13900 | firmware product type, C13901 | firmware compilation date, C13885, C13881, Or if, E timeout time, 13 parameter reference
13
Parameter reference
13.1
Parameters relevant for communication
102
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13885
C13899
C13900
C13901
Parameter | Name:
C13881 | Overall Ethernet Timeout Time
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
Setting of the overall monitoring time (see
Fault with regard to EtherNet/IP communication ( 73)
)
A change in the monitoring response becomes immediately effective.
Setting range
(min. value | unit | max. value)
Lenze setting
500
ms
65535 10000 ms
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear I/O Data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
Setting which I/O data are to be processed by the adapter to maintain internal communication if ...
• the network status of the controlling I/O connection is "Not connected" (see
• an idle event has occurred.
Changes in the setting becomes effective immediately.
Fault with regard to EtherNet/IP communication ( 73)
Selection list
(Lenze setting printed in bold)
0 Use of last Scanner Output Data
1 Clear Scanner Output Data
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Hostname
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
Each subcode contains a string with a length of 32 bytes indicating the designation of the EtherNet/IP node.
(Instance attribute 6 (Host Name) in the
TCP/IP Interface Object (245 / 0xF5) ( 124)
Subcodes
Lenze setting
Info
C13899/1
Host name
C13899/2
Host name
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware Product Type
Data type: VISIBLE_STRING
Index: 10675
d
= 29B3
h
The code contains a string with a length of 8 bytes. The identification code "E84DGYCG" is output.
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13901 | Firmware Compilation Date
Data type: VISIBLE_STRING
Index: 10674
d
= 29B2
h
The code contains a string with a length of 20 bytes. The software creation date ("MMM DD YYYY") and time
("hh:mm:ss") are displayed (e.g. "Mar 21 2005 12:31:21").
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT