3 ac drive object (42 / 0x2a), Ac drive object (42 / 0x2a) ( 135), 14 implemented cip™ objects – Lenze E84Dxxxx User Manual
Page 135
![background image](/manuals/565921/135/background.png)
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
135
14
Implemented CIP™ objects
14.3
"AC Drive Profile" objects
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14.3.3
AC Drive Object (42 / 0x2A)
The "AC Drive Object" describes the device-specific functions of the inverter, e.g. speed ramps,
torque control etc.
Class attributes
Instance attributes
Attribute
ID
Service
Name
Data type
Value
1
Get
Revision
UINT
1 (0x0001)
2
Get
Max. Instance
UINT
1 (0x0001)
3
Get
Number of Instances
UINT
1 (0x0001)
Attribute
ID
Service
Name
Data type
Value
1
Get
NumAttr
USINT
Number of supported attributes
2
Get
Attributes
ARRAY of
USINT
Listing of the supported attributes
3
Get
AtReference
BOOL
1: The inverter currently runs at reference
speed or reference torque (depending on
attribute 6, DriveMode).
4
Get / Set NetRef
BOOL
• 0: Reference via local setting on the device
or terminal
• 1: Reference via network (e.g. from the
scanner)
6
Get / Set DriveMode
USINT
Drive mode:
• 1: Idle speed (frequency)
• 3: Torque control
In order to be able to use the torque control
for the assembly object instances 22 (0x16),
23 (0x17), 72 (0x48), 73 (0x49), this attribute
has to be written.
Write "DriveMode" attribute ( 137)
7
Get
SpeedActual
INT
Current speed
[rpm/2
SpeedScale
]
8
Get / Set SpeedRef
INT
Reference speed
[rpm/2
SpeedScale
]
11
Get
TorqueActual
INT
Current torque
[Nm/2
TorqueScale
]
12
Get / Set TorqueRef
INT
Reference torque
[Nm/2
TorqueScale
]
22
Get / Set SpeedScale
SINT
Speed scaling factor
[Nm/2
SpeedScale
]
Value range: -128 ... 127
24
Get / Set TorqueScale
SINT
Torque scaling factor
[Nm/2
TorqueScale
]
Value range: -128 ... 127
29
Get / Set RefFromNet
BOOL
Status of reference speed / reference torque
• 0: Reference via local setting on the device
or terminal
• 1: Reference via network (e.g. from the
scanner)