C13002 | gateway address, C13003 | mac id, C13005 | ip config control – Lenze E84Dxxxx User Manual
Page 89: C13002, C13005, Code, C13003, 13 parameter reference
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
89
13
Parameter reference
13.1
Parameters relevant for communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13002
C13003
C13005
Parameter | Name:
C13002 | Gateway Address
Data type: UNSIGNED_8
Index: 11573
d
= 2D35
h
Setting of the gateway address
Setting the IP configuration of the Inverter Drive 8400 protec ( 28)
Setting range
(min. value | unit | max. value)
0
255
Subcodes
Lenze setting
Info
C13002/1
0
Gateway address (most significant byte)
C13002/2
0
Gateway address
C13002/3
0
Gateway address
C13002/4
0
Gateway address (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13003 | MAC ID
Data type: OCTET_STRING
Index: 11572
d
= 2D34
h
Display of the MAC-ID
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13005 | IP Config Control
Data type: UNSIGNED_8
Index: 11570
d
= 2D32
h
Selection how the IP configuration is to be effected.
(Instance attribute 3 (Configuration Control) in the
TCP/IP Interface Object (245 / 0xF5) ( 124)
)
Setting the IP configuration of the Inverter Drive 8400 protec ( 28)
Selection list
(Lenze setting printed in bold)
Info
0 Use stored IP
The IP configuration currently stored in the Inverter Drive
8400 protec is used.
1 Use BOOTP
The IP configuration is assigned by the scanner using
BOOTP.
2 Use DHCP
The IP configuration is assigned by the scanner using
DHCP.
The assignment of a gateway address which is not in the
same subnetwork than the IP address, is rejected.
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT