6commissioning – Lenze E84Dxxxx User Manual
Page 28
6
Commissioning
6.3
Setting the IP configuration of the Inverter Drive 8400 protec
28
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3
Setting the IP configuration of the Inverter Drive 8400 protec
IP configuration is necessary in order to assign an address to the Inverter Drive 8400 protec so that
communication between the PC/»Engineer« or the scanner and the inverter is possible via
EtherNet/IP. For this purpose, an IP address, subnet mask and gateway address have to be assigned.
You can assign these IP parameters for the Inverter Drive 8400 protec in the following ways:
•
Setting via the EtherNet/IP configurator of the »Engineer«
•
Setting via codes in the »Engineer«
•
Setting via a BOOTP/DHCP server
•
Setting via the TCP/IP Interface Object (0xF5)
Note!
• The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the EtherNet/IP network can
be established.
(subnet mask),
(gateway address), and
(multicast IP address) show the IP parameters currently used.
• In the case of impermissible settings, the error message
is output.