C00012, C00013, C00039/1 – Lenze E84AVSCx 8400 StateLine C User Manual
Page 39: C00039/2, C00039/3, C00105, 6commissioning

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05
39
6
Commissioning
6.3
Adapting the most important parameters to the drive task
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00012
C00013
C00039/x
C00105
Acceleration time - main setpoint
Acceleration time of the ramp generator for the main speed setpoint
• Time period for the acceleration from standstill to reference speed set in
.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 2.000 s
Deceleration time - main setpoint
Deceleration time of the ramp generator for the main speed setpoint
• Time period for the deceleration from the reference speed set in
to standstill.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 2.000 s
Fixed setpoints 1 ... 3
Fixed speed setpoints (Jog values) for the setpoint generator
• With regard to the reference speed set in
.
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00039/1
40.00 %
Fixed setpoint 1
C00039/2
60.00 %
Fixed setpoint 2
C00039/3
80.00 %
Fixed setpoint 3
Selection/activation of the fixed speed setpoints (Jog values)
In the preset control mode "Terminals 0", the fixed setpoints 1 ... 3 for the "actuating drive speed" are selected via
the digital terminals DI1 and DI2:
DI2
DI1
Speed setpoint =
LOW
LOW
Selection via analog input 1
LOW
HIGH
Fixed setpoint 1
HIGH
LOW
Fixed setpoint 2
HIGH
HIGH
Fixed setpoint 3
Decel. time - quick stop
Deceleration time for the "quick stop" function
• Time period for the deceleration from the reference speed set in
to standstill.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 2.000 s
"Quick stop" function
If the "quick stop" function is activated, the motor control is decoupled from the setpoint selection and within the
deceleration time parameterised in C00105 the motor is brought to a standstill (n
act
= 0).
• The motor is kept at a standstill during closed-loop operation.
• A pulse inhibit (CINH) is set if the auto-DCB function has been activated via C00019.
Activation of the "quick stop" function
• With the device command C00002/17 = "1: On / start".
• In the "Terminals 2" control mode by setting the digital input DI3 to HIGH level.
• In the "Terminals 16" control mode by setting the digital inputs DI3 and DI4 to LOW level (function "fail-safe
selection of direction of rotation").
The "quick stop" function is also activated if the monitoring mode will be enabled the "TroubleQSP" error response
has been parameterised for.