4 process data – INFICON SKY CDGxxxD (Profibus) User Manual
Page 16

16
tira54e1-a (2009-01) CDGxxxD.cp
The structure of the process data part of the input and output data area depends
on the chosen message telegram. Applicable configurations are described below.
When selecting a message telegram, ascertain what output format of the measured
value (integer/float) is required and whether a parameter channel is needed or not.
The gauge can also be operated in such a way that the master does not transmit
any output data to the slave.
Standard
telegram
Master
⇔
Slave
Bytes
Meaning
2
M
⇒ S
0…7 Parameter
Channel
1
S
⇒ M
0
1…2
Exception Status
Process Value UINT16
2
S
⇒ M
0
1…4
Exception Status
Process Value float
7
S
⇒ M
0…7
8
9…10
Parameter Channel
Exception Status
Process Value UINT16
8
S
⇒ M
0…7
8
9…12
Parameter Channel
Exception Status
Process Value float
201
S
⇒ M
0
1…2
3
4…5
Exception Status
Process Value UINT16
Channel Status
Trip Relay 1-2
202
S
⇒ M
0
1…4
5
6…7
Exception Status
Process Value float
Channel Status
Trip Relay 1-2
203
S
⇒ M
0…7
8
9…10
11
12…13
Parameter Channel
Exception Status
Process Value UINT16
Channel Status
Trip Relay 1-2
204
S
⇒ M
0…7
8
9…12
13
14…15
Parameter Channel
Exception Status
Process Value float
Channel Status
Trip Relay 1-2
4.4 Process Data
4.4.1 Standard Telegrams