SECTION 6 - JLG CONTROL SYSTEM
6-8
– JLG Lift –
3121262
Table 6-2. Machine Configuration Programming Information
Configuration Digit
Number
Description
Default
Number
NOTE: The machine configuration must be completed before any personality settings can be changed. Changing
the personality settings first and then changing the model number of the machine configuration will cause
the personality settings to return to default
MODEL NUMBER:
1
0
1
No Model
1500SJ
0
1
ENVELOPE HEIGHT:
2
0
1500SJ: 150' MAX
0
Note: The default settings (bold) will vary depending on the model selection with selection # 5 being the initial default setting.
MARKET:
3
0
1
2
3
4
5
ANSI USA
ANSI EXPORT
CSA
CE
AUSTRALIA
JAPAN
0
ENGINE:
4
1
2
3
4
DEUTZ F4 TIER1: Deutz BF4M1011 Diesel (Tier 1)
DEUTZ F4 TIER2: Deutz BF4M2011 Diesel (Tier 2)
DEUTZ ECM: Engine Control Module
CAT Engine
3
GLOW PLUG:
5
0
1
2
NO GLOW PLUGS: No glow plugs installed.
AIR INTAKE: Glow plugs installed in the air intake on the manifold.
IN-CYLINDER: Glow plugs installed in each cylinder.
2
STARTER LOCKOUT:
6
0
1
DISABLED: Automatic pre-glow time determined by ambient air temperature;
engine start can be attempted at any time during pre-glow.
ENABLED: Automatic pre-glow time determined by ambient air temperature; engine
start is NOT permitted until pre-glow is finished.
0