Phenomenon

Presumed cause and the action







If process variable
(temperature) does
not rise.

• Thermocouple or RTD is burnt out.
[In the case of Thermocouple]

If the input terminal of the instrument is
connected, and if nearby room temperature is
indicated, the instrument should be normal
and sensor may be burnt out.

[In the case of RTD]

If approx. 100

Ω of resistance is connected

to the input terminals between A-B of the
instrument and between B-B is shorted, and
if nearby 0 °C (32 °F) is indicated, the
instrument should be normal and sensor may be
burnt out.

• Lead wire of thermocouple or RTD is not securely

mounted to the instrument terminal.


If it does not

control.

(Indicates only
PV display)

• Program mode is selected.
Î If running by Program mode, press the

OUT

/

OFF

key.

When performing by Fixed value control, press the

key for approx. 3 s while the key is

being pressed to select the Fixed value control
mode. (page 34, 35)

If the main output
or cooling output
has kept its ON
status.

• Main output low limit setting value or cooling

output low limit setting value is set to 100 % or
greater in Auxiliary function setting mode 2.

Î Set the value appropriately. (page 27, 28)

If the main output
or cooling output
has kept its OFF
status.

• Main output high limit setting value or cooling

output high limit setting value is set to 0 % or
less in Auxiliary function setting mode 2.

Î Set the value appropriately. (page 27, 28)

If any unexplained malfunctions occur other than the above mentioned, make inquiries at our agency