Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 29 -
Alarm 1 (A1) action
Mode to select the action Energized or Deenergized
Energized/Deenergized
for Alarm 1.
Selection
[Factory adjusted as Energized]
MODE
This display is not indicated when the rotary switch is set to No. 0
or No. 7 in Alarm 1 action designation (page 12).
Energized
Deenergized
Alarm 2 (A2) action
Mode to select the action Energized or Deenergized
Energized/Deenergized
for Alarm 2.
Selection
[Factory adjusted as Energized]
MODE
This display is not indicated when the rotary switch is set to No. 0
or No. 7 in Alarm 2 action designation (page 12), or the option
[2AS or 2AL] is not applied.
Selection items: The same as those of the alarm 1 (A1) action
Energized/Deenergized
selection.
Alarm 1 hysteresis setting
Mode to set the hysteresis value for Alarm 1.
Setting value
Setting range: 0.1 … 100.0 °C (for TC, RTD inputs)
1 … 1000 (for DC input)
MODE
(Decimal point place follows the selection.)
[Factory adjusted as 1.0 °C]
This display is not indicated when the rotary switch is set to No. 0
or No. 7 in Alarm 1 action designation (page 12).
Alarm 2 hysteresis setting
Mode to set the hysteresis value for Alarm 2.
Setting value
Setting range: 0.1 … 100.0 °C (for TC, RTD inputs)
1 to 1000 (for DC input)
MODE
(Decimal point place follows the selection.)
[Factory adjusted as 1.0 °C]
This display is not indicated when the option [2AS or 2AL] is not
applied and when the rotary switch is set to No. 0 or No. 7 in Alarm 2
action designation (page 12) even if the option [2AS or 2AL] is
applied.