Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 10 -

The following items can be designated by the DIP switch (SW304).
Factory adjusted as all switches OFF [ ].

[Table 3.2-1]

Item

Sw. No

. Designation

Switch

status

Fuzzy self-tuning PID action

No.1: OFF

No.2: OFF

PID action

No.1: ON

No.2: OFF

PD action

No.1: OFF

No.2: ON

Control action

1
and
2

ON/OFF action

No.1: ON

No.2: ON

Heating (reverse) action

No.3: OFF

Heating/Cooling
action

3

Cooling (direct) action

No.3: ON

No standby action

No.4: OFF

Alarm 1 (A1)
standby
action

4

Standby action

No.4: ON

No standby action

No.5: OFF

Alarm 2 (A2)
standby
action (*1)

5

Standby action

No.5: ON

°C

No.6: OFF

°C/°F 6

°F No.6:

ON

K, J, R, B, N, PL-ll, Pt100, JPt100 No.7: OFF

Sensor input

(*2)

7

S, E, T, C, 4 to 20mA, 0 to 20mA,
0 to 1V, Pt100

No.7: ON

Manual start

No.8: OFF

Program start
Auto/Manual

8

Automatic start

No.8: ON


*1: The standby function will not work if the option A2 is not applied.
*2: The sensor input can be designated by the combination of this item and the rotary
switch sensor input (SW303). (See page 11.)

Program start

: This item is available for the program control.

Manual start : Program starts by pressing the

OUT

/

OFF

key.

Automatic start : Program is automatically started by turning the power supply to the

instrument on (after 2 seconds of warm-up status).