WIKA CF1H User Manual
Page 10
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 10 -
The following items can be designated by the DIP switch (SW304).
Factory adjusted as all switches OFF [ ].
[Table 3.2-1]
Item
Sw. No
. Designation
Switch
status
Fuzzy self-tuning PID action
No.1: OFF
No.2: OFF
PID action
No.1: ON
No.2: OFF
PD action
No.1: OFF
No.2: ON
Control action
1
and
2
ON/OFF action
No.1: ON
No.2: ON
Heating (reverse) action
No.3: OFF
Heating/Cooling
action
3
Cooling (direct) action
No.3: ON
No standby action
No.4: OFF
Alarm 1 (A1)
standby
action
4
Standby action
No.4: ON
No standby action
No.5: OFF
Alarm 2 (A2)
standby
action (*1)
5
Standby action
No.5: ON
°C
No.6: OFF
°C/°F 6
°F No.6:
ON
K, J, R, B, N, PL-ll, Pt100, JPt100 No.7: OFF
Sensor input
(*2)
7
S, E, T, C, 4 to 20mA, 0 to 20mA,
0 to 1V, Pt100
No.7: ON
Manual start
No.8: OFF
Program start
Auto/Manual
8
Automatic start
No.8: ON
*1: The standby function will not work if the option A2 is not applied.
*2: The sensor input can be designated by the combination of this item and the rotary
switch sensor input (SW303). (See page 11.)
Program start
: This item is available for the program control.
Manual start : Program starts by pressing the
OUT
/
OFF
key.
Automatic start : Program is automatically started by turning the power supply to the
instrument on (after 2 seconds of warm-up status).