WIKA CF1H User Manual
Page 32
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 32 -
Display selection when
Mode to select the display when the control output is off.
control output is off
Selection
[Factory adjusted as indicating OFF on the PV display]
MODE
OFF is indicated on the PV display.
No indication (all unlit).
Only PV is indicated.
Main setting value
Mode to set the rising rate of the main setting
rising rate setting
value. (Rising value per minute)
Setting value
Setting the value to 0 or 0.0 disables the function.
MODE Setting
range:
0 … 9999 °C/min.
Thermocouple, except T and RTD without
a decimal point
0.0 … 999.9 °C/min. Thermocouple T and RTD with
a decimal point
0 … 9999,
DC input (Decimal point place follows
the
selection.)
[Factory adjusted as 0°C/min.]
Main setting value
Mode to set the falling rate of the main setting
falling rate setting
value. (Falling value per minute)
Setting value
Setting the value to 0 or 0.0 disables the function.
MODE Setting
range:
0 … 9999 °C/min.
Thermocouple, except T and RTD without
a decimal point
0.0 … 999.9 °C/min. Thermocouple T and RTD with
a decimal point
0 … 9999
DC input (Decimal point place follows
the
selection.)
[Factory adjusted as 0 °C/min.]