WIKA CF1H User Manual
Page 72

Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 72 -
 
Phenomenon
Presumed cause and the action
 
 
 
 
 If indication 
 of PV display 
 is abnormal or 
 unstable. 
 • Designation of the Sensor input is improper. 
 Î Set the Sensor input properly by the Rotary switch 
(SW303) and the DIP switch (SW304). 
(page 10, 11) 
 • Temperature unit (°C or °F) is mistaken. 
 Î Set the unit properly by the DIP switch. (page 10) 
 • Sensor correcting value is unsuitable. 
 Î Set the value suitably. (page 23) 
 • Specification of the Thermocouple or RTD is improper. 
 • AC may be leaking into thermocouple or the RTD circuit. 
 • There may be an equipment producing an inductive 
fault or noise near the controller.
 
Phenomenon
Presumed cause and the action
 If setting mode 
 cannot be selected. 
 • Manual control is selected. 
Î
Change the mode to Automatic control (page 36)
 If settings are 
 impossible. 
 If the value does 
 not change by the 
 , keys. 
 • Setting value lock (mode 1 or 2) is designated. 
Î
Release the lock designation. (page 22)
 • During PID auto-tuning. 
Î
Cancel the tuning if necessary. (page 17)
 If the setting 
 indication does not 
 change in the rated 
 scale range even if 
 the , keys 
 are pressed, and 
 setting is impossible. 
 
 
 • Main setting value high limit or low limit may be 
set at the point the value does not change.
Î
Set it again by Auxiliary function setting mode 1.
 If it does not start 
 even if the 
OUT
/
OFF
key
 is pressed in the 
 Program mode. 
 
 • Step time is not set. 
Î
Set the step time. (page 35)