1. Model names
CF1H
-3 A- / M -
- - - ..... Series name CF1H
3
Control
action
PID
(1)
Alarm
A
Process value monitoring, output relay
(2)
R
Relay
S
Logic level (DC 0/12 V) for solid state relay
Output
A
Analogue current signal (4 ... 20 mA)
Input
M
Multi-function input (input configuration settable)
H
AC 100 ... 240 V, 50 ... 60 Hz
Power supply
L
AC/DC
24
V
FT
One-touch mounting bracket (for mounting panel
thickness 1 to 3 mm)
Mounting provision
FS
Screw bracket (for mounting panel thickness 1 to 15
mm)
B
Factory adjustment, device will be configured by the
operator
Instrument configuration
?/#
To customers specification
2AS
(3)
Alarm output 2: process value monitoring
2AR
(3)
Alarm output 2: control loop monitoring
2AL
(3)
Alarm output 2: process value and control loop
monitoring with common terminals
DR2
(4)
2. control output relay
DS2
(4)
2. control output logic level DC 0/12 V
DA2
(4)
2. control output analogue current signal 4 … 20 mA
TA4
(5)
Retransmission output 4 … 20 mA
TV1
(5)
Retransmission output 0 … 1 V
W12
(6)
Heater burnout alarm for 1 phase (max. 20 A)
W15
(6)
Heater burnout alarm for 1 phase (max. 50 A)
W32
(6)
Heater burnout alarm for 3 phase (max. 20 A)
W35
(6)
Heater burnout alarm for 3 phase (max. 50 A)
CR2
(7)
Serial communication RS 232C
CR5
(7)
Serial communication RS 485
EA0
(8)
Remote setting 0 … 20 mA
EA4
(8)
Remote setting 4 … 20 mA
EV0
(8)
Remote setting 0 … 1 V
EV1
(8)
Remote setting 1 … 5 V
SM7
Parameter memory: single parameter settings
external selectable by connection terminals
KAB Terminal
cover
IP4
(9)
IP 54 front protection
Options
P24
Transmitter supply DC 24 V max. 30 mA
(1)
Fuzzy self-tuning PID, PID, PD and ON/OFF action are selectable by internal DIP switch.
(2)
12 types of alarm action and no alarm action are selectable by internal rotary switch and DIP switch.
(3) - (8) Please note that only one option from every group can be selected.
(9)
Condition for this option is the screw type mounting bracket (FS).