Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 31 -
Transmission output selection
Mode to select the type of Transmission output.
Selection
[Factory adjusted as PV transmission]
This display is indicated only when the option
MODE
[TA4 or TV1] is applied.
Process variable (PV) transmission
Main setting value (SV) transmission
Manipulating value (MV) transmission
Transmission output
Mode to set the high limit value of Transmission
high limit setting
output.
Setting value
(In the case of option TA4, the value correponds
to 20mA output.)
MODE
Setting range: Transmission output low limit value
to Input range maximum value
[Factory adjusted as 400 °C]
This display is indicated only when the option
[TA4 or TV1] is applied.
Transmission output when standby:
PV PV, SV 0 value, MV 0 value
Transmission output
Mode to set the low limit value of Transmission
low limit setting
output.
Setting value
(In the case of option TA4, the value corresponds
to 4mA output.)
MODE
Setting range: Input range minimum value to
Transmission output high limit value
[Factory adjusted as 0 °C]
This display is indicated only when the option
[TA4 or TV1] is applied.
Transmission output when standby:
PV PV, SV 0 value, MV 0 value