WIKA CF1H User Manual
Page 28
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 28 -
Cooling action mode selection
Mode to select the Cooling action,
Selection
Air cooling, Oil cooling or Water cooling.
[Factory adjusted as Air cooling]
MODE
This display is indicated only when the option [D 2]
is
applied.
Air cooling (linear characteristic)
Oil cooling (The 1.5th power of Air cooling characteristic)
Water cooling (The 2nd power of Air cooling characteristic)
Cooling output
Mode to set high limit value of the cooling output.
high limit setting
Setting range:
Setting value
Cooling output low limit value to 105 %
Setting greater than 100 % is effective to the type
MODE Current
output.
[Factory adjusted as 100 %]
This display is not indicated when the option [D 2]
is not applied, or when ON/OFF action of cooling side.
Cooling output
Mode to set the low limit value of the cooling output.
low limit setting
Setting range: –5 % to cooling output high limit value
Setting value
Setting less than 0 % is effective to the type Current output.
[Factory adjusted as 0 %]
MODE
This display is not indicated when the option [D 2]
is not applied or when ON/OFF action of cooling side.
Cooling output ON/OFF
Mode to set the ON/OFF action hysteresis of the
action hysteresis setting
cooling control output.
Setting value
Setting range: 0.1 … 100.0 °C
[Factory adjusted as 1.0 °C]
MODE
This display is indicated when the ON/OFF action is
designated in Control action designation and when the
option [D 2] is applied.