WIKA CF1H User Manual
Page 34

Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 34 -
(6) Program mode
In PV/SV display mode, if the key is pressed for approximately 3 seconds while the key is being
pressed, the Program mode can be selected.
The setting value can be increased or decreased by pressing the , and FAST keys.
If the MODE key is pressed, the setting value is registered and the next setting item is selected.
As to the setting values of the step 1 to 7, each setting value for setting value memory number 1 to 7 set
during the Fixed value control is assigned respectively. For example, values in memory number 1 are
assigned to the values for step 1, and number 2 for step 2.
If the Pattern end output is designated and the program control is performed, the Pattern end output is
turned on when the program is completed.
When the Pattern end output is on and if the
OUT
/
OFF
key is pressed, the Pattern end output is turned off. If the
OUT
/
OFF
key is pressed again, the program will be performed.
If some steps are unnecesary, set the times 00.00 for the step numbers not used.
Program Example
Step number (Setting
value memory number)
1 2 3 4 5 6 7
Main setting value
500
500
1000
1000
200
200
100
Proportional band
2.0
1.8
2.0 1.8 2.5 1.8 2.0
Integral
time
180 80 180 80 200 80 200
Derivative
time
30 20 30 20 50 20 50
Proportional
cycle
30 30 30 30 30 30 30
Alarm
1
2 5 2 5 10 0 5
Alarm
2
2 5 2 5 10 0 5
Step time
00:30 01:00 00:40 01:00 02:00 00:30 01:00
0
500
1000