WIKA CF1H User Manual
Page 64
![background image](/manuals/465924/64/background.png)
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 64 -
Control output
Relay
contact
:
1a1b
Control
capacity,
250 V AC, 3 A (resistive load)
250 V AC, 1 A (inductive load cosø=0.4)
Non-contact voltage : For SSR drive
12
+2
,
0
V DC maximum 40 mA DC (short circuit protected)
Current
: 4 … 20 mA DC (Isolated type)
Load resistance, maximum 550
Ω
Controlling action
The fuzzy self-tuning PID, PID, PD or ON/OFF action is selectable by DIP switch.
Fuzzy self-tuning PID action
Proportional
band
(P)
:
Automatic
Integral
time
(I) :
Automatic
Derivative
time
(D) :
Automatic
Anti-reset windup (ARW) : Automatic
Proportional cycle
: 1 … 120 s
Output limiter
: 0 … 100 % (In the case of Current output, –5 … 105 %)
PID action (with auto-tuning function)
Proportional band (P) : 0.1 … 999.9 %
Integral time
(I) : 0 … 3600 s (off when set to 0)
Derivative time
(D) : 0 … 3600 s (off when set to 0)
Anti-reset windup (ARW) : Automatic
Proportional cycle
: 1 … 120 s
Output limiter
: 0 … 100 % (In the case of Current output, –5 … 105 %)
PD
action
Proportional band (P) : 0.1 … 999.9 %
Derivative time
(D) : 0 … 3600 (Off when set to 0)
Proportional cycle
: 1 … 120 s
Reset
: ±Proportional band converted value
When thermocouple or RTD input,
–199.9 … 999.9 °C (°F)
When DC input, –1999 … 9999
(Decimal point place follows the selection.)
Output limiter
: 0 … 100 % (In the case of Current output, –5 … 105 %)
ON/OFF action
Hysteresis setting range :
When thermocouple or RTD input, 0.1 … 100.0 °C (°F)
When DC input, 1 … 1000 (Decimal point place follows the selection.)
Alarm 1 (A1) output
The alarm action point is set by ±deviation to main setting (except Process value alarm).
[When the alarm action is set as energized]
When the input exceeds the range, the output turns ON or OFF
(in the case of High/Low limit range alarm).
[When the alarm action is set as deenergized]
The output acts conversely.
One of the alarms can be selected by rotary switch and DIP switch from 14
types of alarm; High limit alarm, Low limit alarm, High/Low limits alarm,
High/Low limit range alarm, Process high alarm and Process low alarm,
and the standby function is applied to them respectively, as well as
No alarm and Pattern end output.
Setting accuracy : Within ±0.2 % of input range full scale ±1 digit