Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 26 -


(5) Auxiliary function setting mode 2
In PV/SV display mode, if the MODE key is pressed for approx. 3 seconds while the
and keys are being pressed, Auxiliary function setting mode 2 can be selected.
The setting value can be increased or decreased by pressing the , and FAST keys.
If the MODE key is pressed, the setting value is registered and the next setting item is selected.

PV/SV display mode
Actual Main setting
Temperature value

+ + MODE for approx. 3 s

Scaling high limit setting

Mode to set the high limit value of the scaling.

Setting value

If scaling high limit value is changed, main setting

high limit value will be changed to the scaling

MODE

high limit value as well.

Setting range: Scaling low limit value to

input range maximum value

[Factory adjusted as 1370 °C]

Scaling low limit setting

Mode to set the low limit value of the scaling.

Setting value

If scaling low limit value is changed, main setting

low limit value will be changed to the scaling

MODE

low limit value as well.

Setting range: Input range minimum value to

scaling high limit value

[Factory adjusted as –200 °C]

Decimal point place selection

Mode to select the Decimal point place.

Selection

[Factory adjusted as XXXX. (No decimal point)]

MODE

XXXX. (No decimal point)

XXX.X (1-digit below the decimal point)

XX.XX (2-digit below the decimal point)

X.XXX (3-digit below the decimal point)

This display is indicated only when the input

type is selected to DC.