Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 27 -
PV filter time constant
Mode to suppress the PV fluctuation caused by
Setting
such as disturbance.
Setting value
Set the value larger by degrees, and find the setting
value at which the value does not fluctuate.
MODE
If the value is set too large, it affects control result
due to the delay of response.
Setting range: 0.0 … 10.0 s
[Factory adjusted as 0.0 s]
Main output high limit setting
Mode to set the high limit value of the main output.
Setting value
Setting range: Main output low limit value to 105 %
Setting greater than 100 % is effective to the type
MODE
Current output. [Factory adjusted as 100 %]
This display is not available for the ON/OFF action.
Main output low limit setting
Mode to set the low limit value of the main output.
Setting value
Setting range: –5 % to Main output high limit value
Setting less than 0 % is effective to the type Current output.
MODE
[Factory adjusted as 0 %]
This display is not available for the ON/OFF action.
Main output ON/OFF
Mode to set the ON/OFF action hysteresis of the
action hysteresis setting
main control output.
Setting value
Setting range: 0.1 … 100.0 °C
[Factory adjusted as 1.0 °C]
MODE
This display is indicated only when the ON/OFF action
is designated in Control action designation (page10).