WIKA CF1H User Manual
Page 11
![background image](/manuals/465924/11/background.png)
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007
- 11 -
Select the sensor type by rotary switch sensor input (SW303).
Factory adjusted as K, [ ].
[Table 3.2-2]
Rotary Sw.
No.
DIP Sw.
No. 7
Type of
sensor
Scale range
0 OFF K
-200 to 1370°C
-320 to 2500°F
1
OFF
J
-200 to 1000°C
-320 to 1800°F
2
OFF
R
0 to 1760°C
0 to 3200°F
3
OFF
B
0 to 1820°C
0 to 3300°F
4
OFF
PL-ll
0 to 1390°C
0 to 2500°F
5
OFF
N
0 to 1300°C
0 to 2300°F
6
OFF
Pt100
-199.9 to 850.0°C
-199.9 to 999.9°F
7
OFF
JPt100
-199.9 to 500.0°C
-199.9 to 900.0°F
0
ON
S
0 to 1760°C
0 to 3200°F
1
ON
E
0 to 1000°C
0 to 1800°F
2
ON
T
-199.9 to 400.0°C
-199.9 to 750.0°F
3
ON
C (W/Re5-26)
0 to 2315°C
0 to 4200°F
4
ON
4 to 20mAdc
-1999 to 9999
5
ON
0 to 20mAdc
-1999 to 9999
6
ON
0 to 1Vdc
-1999 to 9999
7
ON
Pt100
-200 to 850°C
-320 to 1560°F