Sensor correction function

Corrects the input value from the sensor. When a sensor cannot be set at a location
where control is desired, the sensor measuring temperature may deviate from the
temperature in the controlled location. When controlling with multiple controllers,
the accuracy of sensors have influence on the control. Therefore, sometimes the
measuring temperature (input value) does not concur with the same setting value.
In such a case, the control can be set with desired temperature by shifting the input
value of sensors.


Overlap band/Dead band

Mode to set the Overlap band and Dead band

setting

between Heating control output and Cooling control output.

Setting value

+ setting value: Dead band

MODE

– setting value : Overlap band

Setting range: ± Heating proportional band

converted

value

[Factory adjusted as 0.0 %, Indication: °C]

When the option [D 2] is not applied, or if setting the control

action as ON/OFF, this display is not available.

Remote/Local changing

Mode to change the method (Remote or Local)

Method

to set the Main setting value.

MODE

[Factory adjusted as Local]

Local status. The main setting value can be set

by the front key operation as usual.

Remote status. The main setting value can be

set in analog value by the remote control from external operation.

This display is available only when the option

[EA or EV ] is applied.


Instrument number setting

Mode to set the Instrument number individually

Setting value

to each instrument when communicating by

connecting plural instruments in serial communication.

MODE

Setting range: 0 … 95 [Factory adjusted as 0]

This display is available only when the option [CR2 or CR5]

is

applied.