“Normal Mode Max kW” is the current allowable
“Maximum Power” set for the station in under
normal operating conditions.

Remote Transducers

This section will allow you to enable remote transducers
that are installed. To adjust the

“Enable Remote Sensors”
These are the options available for power
monitoring.

Combo Definitions

This screen allows you to checkmark various combo
options. ‘PSI Start Enable’ and ‘PSI stop Enable’ are
essential. Without these two, the station will not start
stop based on pressure indications. All other check-
marks are need based.

Logic flow enables you to select which zones are
used for flow shutoff. The zones are added together
to provide the flow to compare to the flow shutoff
setpoints.

Figure 61: Combo Definitions

8. [Analog Scaling]

Tap [Analog Scaling] from the Options Setup
Menu.

This screen allows you to scale raw values
into engineering units for analog signal inputs.

Figure 62: Analog Scaling

For each signal such as Pressure, the analog
input values are shown on the left while the
scaled output values are shown on the right.

Figure 63: Analog Scaling Detail

Tap “Names” value to change any of the names
of the variables displayed (Flow, Pressure, etc.).
This can also be used when adding on
functionality to the system. There are a few
‘spare’ I/O names available and those can be
edited to match the new variable for scaling.

Tap [Close] to return to the Options Setup Menu.

9. [Alarm Configuration]

This screen allows you to select various alarm
types from the drop down menu, and fill in the
required settings for each alarm.

Default settings (standard factory settings) can
be found in Appendix D.