Bell & Gossett 10-001-275 XLS Integrated Pump Controller User Manual
Page 15
15
c. “Lockout Setpoint” will display what the Lockout
system has identified as the required set point.
“Remote (Comm)” enable is the setpoint being
communicated by the remote communication
system. The enable box must be checked in
order for the remote communication system to
adjust the system set point.
Figure 3 4 : Setpoint Detail C
d. This portion of the screen will display the Remote
Transducer Settings. The remote transducers are
enabled in the System Setup - Control Options
section. If you have configured/enabled the
remote transducers the “Current” box will display
a value. If not it will show 0.0. By checking the
enable box the system will use the configured
remote transducers.
Figure 3 5 : Setpoint Detail D
e. This portion of the screen displays the Dynamic
Flow Compensation set up.
“Psi Drop” is the setpoint for the calculated
building losses in the system.
“Flow Calc Pacing Time” is the setpoint for the
rate at which the “Current Running Setpoint” will
change due to changes in system flow.
The graph is a representation of system curve
and the cross hairs will display where the station
is currently operating.
Figure 3 6 : Setpoint Detail E
SERVICE
The [SERVICE] tab will take you to the Service detail
screen. From this screen you will be able to access all of
the setup parameters for the station detailed in this
section.
Figure 37: Service Home Screen
1. [Lockout Setup]
Tap [Lockout Setup] from the SERVICE Menu.
The Lockout Setup will allow the station setpoints
to be scheduled during certain periods. An example
of using this parameter would be for scheduling
operation during “unoccupied” periods when
demand will be less.