beautypg.com

[email setup – Bell & Gossett 10-001-275 XLS Integrated Pump Controller User Manual

Page 17

background image

17

3. [Email Setup]

This page allows you to set up email addresses
where Alarm and shutdown messages will be
sent. These emails will notify the user if the
station has shut down or experienced a problem
that the site personnel should be aware of. This
way the user will be notified immediately in case
of a pump station problem. If a fault occurs, an
email will be sent to him.

The email settings can be configured to send
emails to multiple individuals or email addresses.
The vast majority of cell phone providers also
allow email messages to be sent to cell phones
as text messages. A list of known formats is
provided below.

Enable: Check this box to enable email
alarms from the Pace controls.

Use Authentication: Check this box if your
email service requires POP3 authentication.

Note: The POP3 and SMTP servers will usually
have the same address. Enter this value in both
boxes. Sometimes the values are different so
separate boxes have been provided.

To: Enter the email address where the alarm
messages will be sent to. Multiple email
addresses can be entered by separating the
email addresses with a semicolon.

Examples:

[email protected]

;

[email protected]

;

[email protected]

;

[email protected]

.

The following list shows email address formats
for various cell carriers. Sending an email to
these addresses will generate an SMS text
message to the cellular phone

w

here

“phonenumber” is the 10 digit phone number of
the user.

T-Mobile:

[email protected]

Virgin Mobile:

[email protected]

Cingular:

[email protected]

Sprint:

[email protected]

Verizon: [email protected]

Nextel: [email protected]

US Cellular: [email protected]

SunCom: [email protected]

Powertel: [email protected]

AT&T: [email protected]

Alltel: [email protected]

Metro PCS:

[email protected]

SMTP: Enter the IP address of the SMTP
server you will be using. Windows CE devices
require the IP address rather than the server
name.

See “Determining the IP address of the
SMTP

server” in Appendix F for these

instructions.

From: Enter the complete email address
used for this service. Most email servers will
ignore your email request if the “From”
address does not match the account.


Example: [email protected]

User: For most email service providers, enter
the first part of the email address without the
domain name. Note that some providers
require the full email address as your user
name.


Example: mypumpstation

Password: The password to your email
account. Example: Xlem1234

After configuring your email settings, test the
setup.

Tap [Set] to load the information into the
email generator. Then tap [Send]. A test email
will be immediately sent to the address(es)
provided.

If the colored box remains green after hitting
Send, the configurations are working
correctly. If the box turns red there has been
an error. The number after “Status” indicates
the type of error, table for which can be found
in Appendix F.

Additional troubleshooting options for email
configuration can also be found in Appendix
F.