TOTALIZER AUTO RESET

21





This parameter automatically resets the Setpoint Assigned Totalizer (A or B)

each time the setpoint value is reached. The automatic reset can occur at output
start (



) or output end (



). The reset at output end selections will only

appear if the Totalizer Setpoint Action is Timed Out. This reset may be different
from the Totalizer Reset Action selected in Module 4.

SELECTION

ACTION



No Auto Reset



Reset to Zero at the Start of output activation.



Reset to Count Load Value at the Start of output activation



Reset to Zero at the End of output activation (timed out only)



Reset to Count Load at the End of output activation (timed out only)










SETPOINT RESET WHEN SPn+1 DEACTIVATES

SETPOINT RESET WHEN SPn+1 ACTIVATES





Select



, so the setpoint output will deactivate (reset) when SPn +1

activates. (Example: SP1 deactivates when SP2 activates and SP4 when SP1
activates.) The last setpoint will wrap around to the first.





Select



, so the setpoint output will deactivate (reset) when SPn +1

activates and then times out (deactivates). This function may only be used if the
SPn+1 is programmed for Setpoint Action of



. (Example SP1 deactivates

when SP2 is activated and then times out.) The last setpoint will wrap around
to the first.









SETPOINT RESET WITH DISPLAY RESET





Select



, so the setpoint output will deactivate (reset) when the Setpoint

Assignment (



) totalizer display resets. Note: The output will not reset if the

assigned totalizer is reset by a setpoint generated Totalizer Auto reset.





(For Reverse Action, The Alarm state is opposite.)

SETPOINT (ALARM) FIGURES FOR RATE

LOW ACTING WITH NO DELAY

LOW ACTING WITH DELAY

HIGH ACTING WITH TIMEOUT

LOW ACTING WITH TIMEOUT

HIGH ACTING WITH NO DELAY

HIGH ACTING WITH DELAY