16

Select the operating mode for Totalizer A.

SELECTION

MODE

DESCRIPTION



Does not count.



Count X1

Adds Input A falling edge.



Count X1
w/direction

Adds Input A falling edge if Input B is high.
Subtracts Input A falling edge if Input B is low.



Count X1
w/direction*

Adds Input A falling edge if User 1 is high.
Subtracts Input A falling edge if User 1 is low.



Quad X1

Adds Input A rising edge when Input B is high.
Subtracts Input A falling edge when Input B is high



Quad X2

Adds Input A rising edge when Input B is high and
Input A falling edge when Input B is low. Subtracts
Input A falling edge when Input B is high and Input
A rising edge when Input B is low.



Quad X4

Adds Input A rising edge when Input B is high,
Input A falling edge when Input B is low, Input B
rising edge when Input A is low, and Input B falling
edge when Input A is high. Subtracts Input A falling
edge when Input B is high, Input A rising edge
when Input B is low, Input B rising edge when
Input A is high, and Input B falling edge when Input
A is low.



Quad X1*

Adds Input A rising edge when User 1 is high.
Subtracts Input A falling edge when User 1 is high.



Quad X2*

Adds Input A rising edge when User 1 is high and
Input A falling edge when User 1 is low. Subtracts
Input A falling edge when User 1 is high and Input
A rising edge when User 1 is low.



Count X2

Adds Input A rising and falling edges.



Count X2
w/direction

Adds Input A rising and falling edges if Input B is
high. Subtracts Input A rising and falling edge if
Input B is low.



Count X2
w/direction*

Adds Input A rising and falling edges if User 1 is
high. Subtracts Input A rising and falling edge if
User 1 is low.

* Dual Count mode (

), where Inputs A and B are both used for count

signals. User 1 accepts Input A direction or quadrature signal.

16





TOTALIZER A OPERATING MODE















 



 

Totalizer x

Reset Action

Totalizer x

Decimal
Position

Totalizer x

Scale Factor

Totalizer x

Count Load

Value

Totalizer x

Reset at

Power-up

x

tot

Totalizer x

Operating

Mode

PAR

4-tot

x

rESEt

x

SCFAC

x

CntLd

x

P-UP

Pro

x

dECPt

x

SCALr

Totalizer x

Scale

Multiplier

6.4 MODULE 4 - T

OTALIZER

A & B S

ETUP

P

ARAMETERS

(



)

PARAMETER MENU

x = Totalizer A or B

Module 4 is the programming for Totalizer A and Totalizer B. Totalizer B parameters follow Totalizer A. For maximum input frequency, the
totalizers should be set to mode NONE when they are not in use. When set to NONE, the remaining related parameters are not accessible.
A corresponding annunciator indicates the totalizer being shown in the Display Mode. An Exchange Parameter Lists feature for scale factors
and count load values is explained in Module 2.





TOTALIZER A RESET ACTION

When Totalizer A is reset, it returns to zero or Totalizer A count load value.

This reset action affects all Totalizer A resets, except the Setpoint Totalizer Auto
Reset in Module 6.







TOTALIZER A DECIMAL POSITION

This selects the decimal point position for Totalizer A, Totalizer A Count

Load Value, and any setpoint value assigned to Totalizer A. The selection will
also affect Totalizer A scale factor calculations.

When Totalizer C is enabled, this setting applies to both Totalizer A and B

displays (same position for both). If Totalizer C is disabled, separate decimal
point positions can be selected for Totalizer A and Totalizer B.





TOTALIZER A SCALE FACTOR

The number of input counts is multiplied by the scale factor and the scale

multiplier to obtain the desired process value. A scale factor of 1.00000 will
result in the display of the actual number of input counts. (Details on scaling
calculations are explained at the end of this section.)



to















TOTALIZER A SCALE MULTIPLIER

The number of input counts is multiplied by the scale multiplier and the scale

factor to obtain the desired process value. A scale multiplier of 1 will result in
only the scale factor affecting the display. (Details on scaling calculations are
explained at the end of this section.)





TOTALIZER A COUNT LOAD VALUE

When reset to count load action is selected, Totalizer A will reset to this

value.





TOTALIZER A RESET AT POWER-UP

Totalizer A may be programmed to reset at each meter power-up.



to









