Chapter 6 ____________________________________________________________ Troubleshooting

VAISALA ________________________________________________________________________ 63

Problem or Message

Likely Causes and Solutions

Cannot connect to serial line,

current serial settings of the

module are unknown.

Perform the following steps to connect:

1. Set your terminal settings to 19200 8 N 1 (the

default settings of the module).

2. Connect to the service port of the module.

2. Power up the module, and type "z" on the serial

line at least five times.

4. The module will come online with the default

settings, and with the text SERVICE MODE.

5. Use the

SERI command to set the desired

serial settings, and use the

SAVE command to

save them.

Any of the following errors is

active:

- Program checksum error

- Parameter storage

checksum error

- Sensor coefficient checksum

error

- Current settings checksum

error

- Default settings checksum

error

- Log corrupted

- Resistance measurement

Internal error. Perform the following steps:

1. Reset or power cycle the module. Check if the

error is gone.

2. Return the module to factory settings using the

FRESTORE command. Check again.

3. If the error is still active, contact a Vaisala

service center.

Technical Support

For technical questions, contact the Vaisala technical support by e-mail at

[email protected]

. Provide at least the following supporting

information:

- Name and model of the product in question
- Serial number of the product
- Name and location of the installation site
- Name and contact information of a technically competent person who

can provide further information on the problem.

Product Returns

If the product must be returned for service, see

www.vaisala.com/returns

.

For contact information of Vaisala Service Centers, see

www.vaisala.com/servicecenters

.