Outback Power Systems VFX Series Programming Manual User Manual

Page 53

background image

52

ADV/FX/AUX----------------P00

ventfan 13.0 vdc

on setpoint

DOWN INC DEC PORT

When the AUX is set to ventfan, a fan ventilates

a battery enclosure. The ventfan on setpoint

establishes the battery voltage which energizes

the AUX and thus the fan for a one minute period.

The voltage setting has a range of 10.0 VDC-16.0

VDC using and . Recharging

causes batteries to emit mostly hydrogen gas;

higher recharging voltages emit more gas.

Press to view the ventfan off period screen.

ADV/FX/AUX----------------P00

loadshed 11.0 vdc

off setpoint

DOWN INC DEC PORT

The loadshed off setpoint battery voltage triggers

the AUX to reduce the inverter and battery loads.

When the battery voltage drops below this value

for three seconds, the AUX powers a DC coil relay

to disconnect an AC load. Once triggered,

loadshed remains on for at least three minutes.

The loadshed off setpointis adjustable from10 VDC-

14 VDC using and . Press

to bring up the ventfan on setpoint.

ADV/FX/AUX----------------P00

genalert 9 min

off delay

DOWN INC DEC PORT

After a battery has recharged or returned to

the genalert off setpoint, genalert off delay

determines the amount of time the generator

remains on to assure the battery has been more

fully recharged. The user can adjust this time from

0-240 minutes using and .

Press to view the loadshed off setpoint

screen.

ADV/FX/AUX----------------P00

ventfan off 5 min

period

DOWN INC DEC PORT

If a ventilation fan is only needed intermittently,

the ventfan off period shuts the fan off for a

user-determined time before starting up again

for a one-minute period when the battery

voltage exceeds the ventfan on setpoint. This

off period can be set from 0-30 minutes using

and . Setting this period to zero will

keep the fan running the entire time the battery

voltage is high enough to activate the ventfan

function. Setting it to fi ve minutes means the fan

will run for one minute and then shut off for fi ve

minutes until the battery voltage drops and the

fan is no longer needed. Press to view the

diversion on setpoint screen.

INC

DEC

DOWN

INC

DEC

DOWN

INC

DEC

DOWN

INC

DEC

DOWN