beautypg.com

Outback Power Systems VFX Series Programming Manual User Manual

Page 15

background image

14

ADV/FX/CHARGER---------P00

absorb

01.0 hrs

time limit

DOWN INC DEC PORT

ADV/FX/CHARGER---------P00

fl oat 13.6 vdc
setpoint

DOWN INC DEC PORT

ADV/FX/CHARGER---------P00

fl oat 01.0 hrs
time period

DOWN INC DEC PORT

ADV/FX/CHARGER---------P00

refl oat 12.2vdc
set point

DOWN INC DEC PORT

The absorb time limit must be long enough for

the batteries to regain 95-100% of their charge.

This time limit can be set between 0 hours and 24

hours using

and . The FX auto-

matically reduces this limit when it’s connected to

a partially charged battery. Press

to

continue in the CHARGER Menu.

The fl oat set point is the batteries’ fi nishing charge

which completes the recharging process. This

setting ranges from 12.0VDC to 15.0VDC. Press

to continue.

The fl oat time period is the amount of time—from

0 to 24 hours— the recharging process maintains

the fl oat set point. Larger batteries will probably

require more time than smaller batteries. The

recharging stops when the fl oat time period is

satisfi ed. Press to view the next screen.

When the battery voltage falls below the refl oat

set point, a fl oat cycle recharging starts. This can

act as a maintenance recharging or a recharging

when intermittent DC loads are running and an

AC source is available for recharging. This setting

ranges between 12.0VDC and 13.0VDC. Press

to view the next CHARGER screen.

INC

DEC

DOWN

DOWN

DOWN

DOWN