ADV/FX/GEN---------------P00

ac2/gen 108 vac
lower limit

DOWN INC DEC PORT

ADV/FX/GEN---------------P00

ac2/gen 140 vac
upper limit

DOWN INC DEC PORT

ADV/FX/GEN---------------P00

ac2/gen 7.0 aac
input limit

DOWN INC DEC PORT

ADV/FX/GEN---------------P00

ac2/gen 60 cycles
transfer delay

DOWN INC DEC PORT

The ac/2 gen lower limit is the lowest allowable

voltage for the FX to connect to the generator.

If the voltage falls below this limit, the FX will

disconnect from the generator. This voltage value

is adjusted using and for values

between 40VAC and 115VAC. Press to

continue viewing the generator screens

The ac2/gen upper limit is the highest allow-

able voltage for the FX to remain connected to

the generator. If the voltage is higher than this

limit, the FX will disconnect from the generator.

This voltage value is adjusted using and

for values between 130 VAC and 150 VAC. Press

to view the ac2/gen input limit screen.

The ac2/gen input limit is the maximum current

the FX can draw from a generator. When this limit

is reached, the FX reduces its battery charging

function to prevent overloading the generator. If

the generator exceeds this limit, the FX will start

blinking the red ERROR LED as a warning. This

setting’s range is 2.0AAC to 30.0AAC, adjustable

using using and . Press

to continue.

The ac2/gen transfer delay is the amount of

time the FX remains connected to the genera-

tor after the AC input voltage drops below the

ac2/gen lower limit setting. This setting is adjusted

between 0 and 240 cycles using and

Press the soft key to view the next GEN

screen.