STACKING OPTIONS

OutBack FXs can be stacked in one of fi ve diff erent confi gurations:

1. OutBack Parallel

2. Classic Series

3. OutBack Series

4. OutBack Series/Parallel

5. 3-Phase

Note: Although stacking 10 FXs is possible, OutBack’s AC hardware only accommodates confi gurations

of two, four, or eight FXs. A system with eight FXs would require two AC Input/Output Bypass (IOB)

Assembly Kits or installing an external manual bypass; ten FXs would require three IOB kits or an

external manual bypass.

1. Outback Parallel

• 2-10 FXs are wired to the same 120VAC output leg or phase.

• The Slave FXs can be programmed to remain at diff erent power levels (“Silent” or “On” depending on

the need) to save energy; the Slaves will come on when the power demand requires them.

• This power-saving system is fully automatic and works with or without a MATE connected to the

system, although a MATE is required to program the components. Without a MATE, the user cannot

reprogram.

• The AC input (generator or grid) must be 120VAC.

2. Classic Series

• Two FXs are wired to two 120VAC output

legs producing 240VAC between them.

• Each FX powers one leg and acts

independently of the other, but both

combine when 240VAC is required for a load.

• The AC input (generator or grid) must be 240

split-phase

VAC.

3 kW

120 VAC

Leg 2

3 kW 120 VAC

3 kW 120 VAC

LOAD

3 kW

120 VAC

Leg 1

6 kW

120 VAC

Leg 1

and

Leg 2

or

3 kW

120 VAC

Leg 2